Transmitter DULCOMETER DMTa

The transmitter DULCOMETER DMTa converts the sensor signals for pH, ORP value, chlorine concentration and conductivity into an interference-insensitive 4-20 mA analogue signal. Flexible, safe and always the optimum resolution of measured value.

The Compact 2-Wire Transmitter – the Link to the PLC and DULCOMETER.

The 2-wire transmitter DMTa converts the following sensor signals into an interference-insensitive 4-20 mA analogue signal: pH, ORP, temperature, chlorine and conductivity.

It is fed via the 2-wire analogue input of a PLC or via a 2-wire analogue input of a ProMinent controller. The 4-20 mA analogue current proportional to the measured value is transmitted via the same two lines.

The DMTa offers an on-site calibration option of the sensor and galvanic separation between the sensor input and measured value output.

Your Benefits

  • Flexibility in the choice of measured variable with pH, ORP and temperature
  • Excellent operational safety, thanks to sensor monitoring (pH)
  • Galvanic isolation between the sensor and supply
  • Always the optimum measured value resolution by auto-ranging with conductivity measurement
  • Safety through sensor monitoring of pH for glass breakage and line breakage
  • Various installation options: wall-mounted, installation on an upright or in a control cabinet

Technical Details

  • Measured variables: pH, ORP, chlorine, temperature and conductivity
  • Precision: 0.5 % of the measuring range limit value
  • Correction variable: Temperature via Pt 100/Pt 1000 (pH, chlorine, conductivity)
  • Communication interface: PROFIBUS DP (wall-mounted only)
  • Degree of protection: IP 65 (wall-mounted, pipe-mounted), IP 54 (installation in a control cabinet)
  • Display: Graphic display

Technical Data

Measuring range

pH – 1.00 … 15.00
-1200 … +1200 mV redox potential
0.01 … 50.0 mg/l Chlorine
-20 … +150 °C
1 µS/cm … 200 mS/cm (auto-ranging), depending on the cell constant

Cell constant

0.006 … 12.0/cm for conductivity

Resolution

0.01 pH
1 mV
0.1 % of measuring range for chlorine
0.1 °C
Conductivity 1/1000 of display value (min. 0.001 μS/cm)

Accuracy

0.5% from measurement range

Measurement input

mV terminal (pH, ORP); input resistance > 5 x 1011 Ω
Chlorine terminal (DMT chlorine sensors)
Pt 100/1000 terminal
Conductivity terminal (2 or 4-line connection)

Correction variable

Temperature via Pt 100/1000 (pH, chlorine, conductivity)

Correction range temp.

Chlorine: 5 … 45 °C, pH: 0 … 100 °C, conductivity: 0 … 100 °C

Min. current loop

4 mA

Max. current loop

20 mA

Fault current

23 mA

Feed voltage

2-wire transmitter, 16… 35 V DC, nominal 24 V
PROFIBUS DP design, 16… 30 V DC, 24 V nominal

Communication interface

PROFIBUS DP (wall-mounted only)

Min. ambient temperature

0 °C

Max. ambient temperature

55 °C

Climate

Relative humidity up to 95% (non-condensing)

Enclosure rating

IP 65 (wall-mounted, pipe-mounted)
IP 54 (installation in a control cabinet)

Display

graphical display

Housing material

PPE

Dim. H

135 mm

Dim. B

125 mm

D dimension

75 mm

Weight

0.45 kg